Department for Work and Pensions, Stockton: 11.5% less electricity on the client's own meter

SavaPower voltage optimisation case study. Metered, 2013 (historical).

At a glance
ClientDepartment for Work and Pensions (DWP), office in Stockton-on-Tees
SectorCentral government offices
ProductSavaPower voltage optimisation, one three-phase system on the whole building supply
Unit size250 A
Test periodInstalled July 2013. Week ending Tuesday 6 August 2013 in bypass against week ending Tuesday 13 August 2013 with SavaPower on
Result11.5% less electricity (1,056 kWh in the week). Metered on the client's own half-hourly meter, using a bypass test. Historical, 2013
11.5%
less electricity with SavaPower on than in bypass
Metered on the client's own half-hourly meter, August 2013 (historical)
9,173 kWhweek in bypass
8,117 kWhweek with SavaPower on
1,056 kWhless, same seven weekdays

The bypass week began warmer; on the two weekdays with similar weather the saving was 9.7%.

SavaPower switching unit and red transformer unit installed beside the main switchboard at a DWP office in Stockton-on-Tees

The problem

Voltage optimisation is easy to claim and hard to prove. An office’s consumption moves with the weather and occupancy, so a simple before-and-after comparison can flatter or hide the real effect.

DWP already knew SavaWatt: savacontrol had been fitted at several hundred DWP sites over a number of years. DWP then chose SavaWatt for voltage optimisation, with this four-storey office as the trial site. In all, SavaWatt has fitted over 200 SavaPower voltage optimisation units at DWP sites nationwide.

What was installed

A SavaPower voltage optimisation system, rated 250 A, on the supply to the whole building: a switching unit with a true electrical bypass, and an energy saving transformer. The client’s meter shows the supply off for about two and a half hours on the evening of 26 July 2013 while it was connected. Supply voltage fell from an average of 247 V to 222.5 V, about 10%.

SavaPower controller showing 221 V supplied to the building against 246 V incoming
The SavaPower controller during the trial: 221 V supplied to the building, 246 V incoming.
SavaPower switching unit and transformer unit, DWP Stockton, 2013

Supply voltage: 247.0 V in bypass, 222.5 V with SavaPower on

21022023024025027 Jul29 Jul31 Jul2 Aug4 Aug6 Aug8 Aug10 Aug12 Aug14 AugSwitched to bypass, about 15:45 Wed 31 JulBack on, about 15:00 Wed 7 Aug Bypass: average 247.0 V SavaPower on: average 222.5 V SavaPower onVolts 21022023024025027 Jul31 Jul4 Aug8 Aug12 AugShaded: bypass, from about 15:45 Wed 31 Julto about 15:00 Wed 7 Aug Bypass: 247.0 V SavaPower on: average 222.5 V Volts

Metered data: SavaWatt’s logger on the building’s incoming supply, one reading every 30 or 60 seconds, shown as hourly averages, 27 July to 14 August 2013. Shaded: SavaPower in bypass.

How the saving was measured

The figures come from the client’s own half-hourly meter, through their energy monitoring portal, supplied by their energy team. SavaWatt’s equipment played no part in the headline.

Because SavaPower has a bypass, the unit could be switched out and back in without a shutdown. It was switched to bypass on 31 July 2013, so the building ran on full mains voltage for a week, then back into circuit on 7 August. We compared the full week ending Tuesday 6 August (bypass) with the full week ending Tuesday 13 August (SavaPower on): seven days against seven, the same weekdays. We did not calculate a saving; we turned the unit off and on again and let the client’s meter show it.

Two weeks on the client's meter, Wednesday to Tuesday

Bypass week, Wed 31 Jul to Tue 6 Aug 2013: 9,173 kWh SavaPower on, Wed 7 to Tue 13 Aug 2013: 8,117 kWh0204060Wed31 Jul / 7 AugThu1 Aug / 8 AugFri2 Aug / 9 AugSat3 Aug / 10 AugSun4 Aug / 11 AugMon5 Aug / 12 AugTue6 Aug / 13 AugkWh per half-hour Bypass week to 6 Aug: 9,173 kWh SavaPower on, to 13 Aug: 8,117 kWh0204060WedThuFriSatSunMonTuekWh per half-hour
Daily electricity use, kWh, from the client's weekly reports
DayBypass week (to 6 Aug)SavaPower on (to 13 Aug)
Wed1,4281,399
Thu1,6121,418
Fri1,6391,451
Sat710557
Sun809605
Mon1,5231,359
Tue1,4521,327
Week9,1738,117

Daily figures are rounded, as printed on the client's two weekly reports; the week totals are the reports' own totals. Difference: 1,056 kWh, 11.5%.

Metered data. Source: the client’s own half-hourly metering, every half-hour of both weeks (export run 15 August 2013). Grey: SavaPower in bypass. Crimson: SavaPower on.

Results

Result of the bypass test at DWP Stockton, August 2013
MeasureWithout (bypass)With SavaPowerSavingStatus
Whole building, 7 days against 7, client's half-hourly meter9,173 kWh8,117 kWh1,056 kWh, 11.5%Metered by the client, 2013

Consumption fell on every day, at night as well as in office hours. The bypass week began warmer, adding air conditioning load; on the two weekdays with similar weather the saving was 9.7%. Other readings of the same test were higher: 13.4% on the client portal’s comparison with the previous four weeks, and 14.35% on SavaWatt’s one-minute logger. We lead with 11.5% because it is the full-week, like-for-like comparison on the client’s own meter, and anyone can check it from the two weekly reports.

What it means for similar sites

  • Ask for a bypass test on your own meter. A result you can switch off and on is worth more than a calculation.
  • Savings vary by site and load. This result sits within the range we have metered on SavaPower sites, 9.68% to 18.9%.
  • Installation needs a full shutdown of about two hours, arranged for when the building is closed; after that, settings can be changed through the bypass without another shutdown.
  • Warranty: five years parts and labour, ten years on transformers.

Compare Nuffield Health, Cheam (11.16% on a billing meter) and Iceland Foods, or see the earlier DWP refrigeration and air conditioning controls programme and our government and council case studies. More on SavaPower voltage optimisation.

Questions about this case study

11.5%: 1,056 kWh less in a week with SavaPower on than in the week before, in bypass (August 2013).

By switching the building between SavaPower and bypass and comparing a full week of each on the half-hourly meter.

The data is the client’s own, from their metering portal, not SavaWatt’s equipment. No third party audited the analysis.

They cover different days and weather, so we lead with the full-week comparison.

It is a historical result from 2013. Savings depend on each site’s voltage and load, so every quote starts with a survey.