SavaPower voltage optimisation case study. Metered, 2013 (historical).
| Client | Department for Work and Pensions (DWP), office in Stockton-on-Tees |
|---|---|
| Sector | Central government offices |
| Product | SavaPower voltage optimisation, one three-phase system on the whole building supply |
| Unit size | 250 A |
| Test period | Installed July 2013. Week ending Tuesday 6 August 2013 in bypass against week ending Tuesday 13 August 2013 with SavaPower on |
| Result | 11.5% less electricity (1,056 kWh in the week). Metered on the client's own half-hourly meter, using a bypass test. Historical, 2013 |
The bypass week began warmer; on the two weekdays with similar weather the saving was 9.7%.
Voltage optimisation is easy to claim and hard to prove. An office’s consumption moves with the weather and occupancy, so a simple before-and-after comparison can flatter or hide the real effect.
DWP already knew SavaWatt: savacontrol had been fitted at several hundred DWP sites over a number of years. DWP then chose SavaWatt for voltage optimisation, with this four-storey office as the trial site. In all, SavaWatt has fitted over 200 SavaPower voltage optimisation units at DWP sites nationwide.
A SavaPower voltage optimisation system, rated 250 A, on the supply to the whole building: a switching unit with a true electrical bypass, and an energy saving transformer. The client’s meter shows the supply off for about two and a half hours on the evening of 26 July 2013 while it was connected. Supply voltage fell from an average of 247 V to 222.5 V, about 10%.
Metered data: SavaWatt’s logger on the building’s incoming supply, one reading every 30 or 60 seconds, shown as hourly averages, 27 July to 14 August 2013. Shaded: SavaPower in bypass.
The figures come from the client’s own half-hourly meter, through their energy monitoring portal, supplied by their energy team. SavaWatt’s equipment played no part in the headline.
Because SavaPower has a bypass, the unit could be switched out and back in without a shutdown. It was switched to bypass on 31 July 2013, so the building ran on full mains voltage for a week, then back into circuit on 7 August. We compared the full week ending Tuesday 6 August (bypass) with the full week ending Tuesday 13 August (SavaPower on): seven days against seven, the same weekdays. We did not calculate a saving; we turned the unit off and on again and let the client’s meter show it.
| Day | Bypass week (to 6 Aug) | SavaPower on (to 13 Aug) |
|---|---|---|
| Wed | 1,428 | 1,399 |
| Thu | 1,612 | 1,418 |
| Fri | 1,639 | 1,451 |
| Sat | 710 | 557 |
| Sun | 809 | 605 |
| Mon | 1,523 | 1,359 |
| Tue | 1,452 | 1,327 |
| Week | 9,173 | 8,117 |
Daily figures are rounded, as printed on the client's two weekly reports; the week totals are the reports' own totals. Difference: 1,056 kWh, 11.5%.
Metered data. Source: the client’s own half-hourly metering, every half-hour of both weeks (export run 15 August 2013). Grey: SavaPower in bypass. Crimson: SavaPower on.
| Measure | Without (bypass) | With SavaPower | Saving | Status |
|---|---|---|---|---|
| Whole building, 7 days against 7, client's half-hourly meter | 9,173 kWh | 8,117 kWh | 1,056 kWh, 11.5% | Metered by the client, 2013 |
Consumption fell on every day, at night as well as in office hours. The bypass week began warmer, adding air conditioning load; on the two weekdays with similar weather the saving was 9.7%. Other readings of the same test were higher: 13.4% on the client portal’s comparison with the previous four weeks, and 14.35% on SavaWatt’s one-minute logger. We lead with 11.5% because it is the full-week, like-for-like comparison on the client’s own meter, and anyone can check it from the two weekly reports.
Compare Nuffield Health, Cheam (11.16% on a billing meter) and Iceland Foods, or see the earlier DWP refrigeration and air conditioning controls programme and our government and council case studies. More on SavaPower voltage optimisation.
11.5%: 1,056 kWh less in a week with SavaPower on than in the week before, in bypass (August 2013).
By switching the building between SavaPower and bypass and comparing a full week of each on the half-hourly meter.
The data is the client’s own, from their metering portal, not SavaWatt’s equipment. No third party audited the analysis.
They cover different days and weather, so we lead with the full-week comparison.
It is a historical result from 2013. Savings depend on each site’s voltage and load, so every quote starts with a survey.
Send us a recent bill and, if you have it, half-hourly data. Our free savings survey and quote gives an expected range with a stated worst case, the cost and payback, and how the saving would be verified.