Case study: SavaPower voltage optimisation
| Client | True Potential, Newburn Riverside, Newcastle upon Tyne |
|---|---|
| Sector | Offices (financial services) |
| Product | SavaPower voltage optimisation, one unit per building |
| Units | Gateway House (new building): 250 A |
| Test | Both buildings switched to bypass from 25 September to 2 October 2026 (seven days) |
| Results | Newburn House: 9.3% less electricity, metered (18 September to 1 October 2026). Gateway House: about 3% less over the whole day, metered, and about 8% lower overnight load, midnight to 5am, nights only (25 September to 2 October 2026, compared with the weeks either side) |
| Year | Installed 2026; measured 2026 |
Newburn House (existing headquarters)
less electricity, whole building. Metered
Gateway House (new building)
less across the whole day. Metered
Overnight (midnight to 5am) the Gateway House load was about 8% lower: metered, nights only, not the building’s saving.
True Potential runs two offices side by side in Newcastle: Newburn House, its existing headquarters, and Gateway House, a new office next to it. Each building has its own supply, and the incoming voltage at both was around 243 to 244 V, well above the 230 V that office equipment is designed for. The question was simple: how much would lowering it save in each building, measured rather than estimated?
A SavaPower unit was fitted in each building: in Gateway House during its fit-out, and in Newburn House as part of its refurbishment. SavaPower uses a multi-tap transformer to bring the supply down to a lower, fixed voltage, with a bypass that can return the building to normal mains. Settings are changed by hand, and because of the bypass they can be changed without another shutdown.
The warranty is five years on parts and labour and ten years on transformers.
Each SavaPower unit logs power, voltage and energy every minute. On 25 September 2026 both units were switched to bypass for seven days, then back to saving mode on 2 October. The bypass lets the same building be compared with itself, which gives a real measured comparison rather than a projection.
With SavaPower on, the supply was 223.6 V at Gateway House and 225.7 V at Newburn House. In bypass it was 244.2 V and 243.7 V.
Like was compared with like: the same hours of the day, and for Gateway House the same weekdays in the weeks either side of the test. All figures come from SavaWatt’s own metering in the units, not the client’s billing meter.
Because SavaPower has a bypass, the saving can be proved by switching the unit off and on again.
Load in each building, hour by hour, before, during and after the bypass week.
Metered data: hourly averages of one-minute readings from the SavaPower logger in each unit, 18 September to 9 October 2026. Shaded: the bypass week, 25 September to 2 October 2026. Gaps are missing readings. Average levels are for the matched hours used in each building’s result.
Each building is reported on its own. The two results are never added together or averaged.
| Building | What was measured | Saving | Status |
|---|---|---|---|
| Newburn House (older HQ) | Whole-building electricity, 154 hours of bypass against the week before, hour by hour | 9.3% | Metered |
| Gateway House (new building) | Whole-building electricity, 168 hours of bypass against the week before and the week after, same weekday and hour | about 3% (2.9%) | Metered |
| Gateway House (new building) | Overnight load only, 00:00 to 05:00, 7 bypass nights against the nights in the week before and the week after | about 8% (12.39 kW in bypass, about 11.4 kW with SavaPower on) | Metered, nights only |
Two buildings on one site, with a similar voltage reduction, gave different results. At Gateway House the saving came mainly at night and early in the morning; during the working day the load barely changed. At Newburn House, other fair comparisons of the same data gave between 7.7% and 15.7%, because refurbishment works were running during the test week.
That is why we do not quote one percentage for SavaPower: the saving depends on the building and what it runs, and the survey assesses that before any quote.
Metered: supply voltage logged by each SavaPower unit in bypass and with SavaPower on; whole-building saving from the bypass test, 2026.
Annualised from the one-week test, not measured over a year.
a year for the two buildings. Annualised from the test week
a year at 25p per kWh, SavaWatt’s illustrative rate, not the client’s tariff. Annualised from the test week
of CO2 a year at 0.233 kg per kWh, the factor used in SavaWatt’s 2026 literature. Annualised from the test week
By building: Newburn House about 21,500 kWh a year; Gateway House about 7,900 kWh a year. Both annualised from the test week.
In Newburn House, 9.3% of the building’s electricity, metered in a bypass test in September and October 2026. In Gateway House, about 3% over the whole day, with the overnight load (midnight to 5am) about 8% lower.
Each building was switched to bypass for seven days and compared with the same hours with SavaPower on, using the one-minute metering in the SavaPower units.
The voltage reduction was similar, but the buildings run different equipment in different ways. Savings vary by site and load, so we survey a building before quoting.
No. The figures come from SavaWatt’s metering in the units. Because SavaPower has a bypass, a client can repeat the test on its own meter.
Compare with DWP Stockton and Nuffield Health, Cheam, or see more case studies.
Send us a recent bill and, if you have it, half-hourly data for your building. Our free savings survey and quote lists the equipment, the cost, the payback and the carbon saving, with an expected range and a stated worst case.